. . "1"^^ . "Network configuration impact on during-fault voltage in distribution system"@en . . . . . "RIV/49777513:23220/12:43915489!RIV13-MSM-23220___" . "Network configuration impact on during-fault voltage in distribution system"@en . "Network configuration impact on during-fault voltage in distribution system" . "Network configuration impact on during-fault voltage in distribution system" . . "local generator; power line; network configuration; short-circuit; sag; voltage dip; power quality; distribution system"@en . . . . . . "23220" . "1"^^ . "RIV/49777513:23220/12:43915489" . "[4C18CE31E495]" . . "The changes in the supply network configuration can significantly influence the voltage at individual sites during fault events. The paper deals with an impact of the network configuration on the voltage dip magnitude, especially with the impact of a network operated in a radial way, a network with loop lines or parallel lines, and the impact of a spot network or a on-site (local) generator. Equations and graphs concerning with the above issues are derived. Their validation is made on the case of a real 110 kV network, partially meshed." . "I" . . . . . "The changes in the supply network configuration can significantly influence the voltage at individual sites during fault events. The paper deals with an impact of the network configuration on the voltage dip magnitude, especially with the impact of a network operated in a radial way, a network with loop lines or parallel lines, and the impact of a spot network or a on-site (local) generator. Equations and graphs concerning with the above issues are derived. Their validation is made on the case of a real 110 kV network, partially meshed."@en . "153829" . "Tesa\u0159ov\u00E1, Miloslava" . . . .