"Jaro\u0161, Michal" . . . "Simulace tepeln\u00E9 pohody v n\u00EDzkoenergetick\u00E9m rodinn\u00E9m dom\u011B s teplovzdu\u0161n\u00FDm vyt\u00E1p\u011Bn\u00EDm."@cs . "The paper deals with the simulation of thermal comfort in a central living room of a low-energy family house with warm-air heating. This topic follows from existing low experience with this heating system in the Czech Republic. Airflow velocities and draught risk (DR) after CSN EN ISO 7730 were evaluated here. The velocities below 0,2 m/s were assessed in the most area in the height of 10 cm above the floor. Corresponding DR values up to 20 % indicate possible draught feeling. Conditions in the height of 110 cm above the floor are much more favourable - the DR values are mostly negligible there."@en . . "Simulace budov a techniky prost\u0159ed\u00ED: Sborn\u00EDk 5. konference IBPSA-CZ" . . . . "SIMULATION OF THERMAL COMFORT IN A LOW-ENERGY FAMILY HOUSE WITH WARM-AIR HEATING"@en . "Simulace tepeln\u00E9 pohody v n\u00EDzkoenergetick\u00E9m rodinn\u00E9m dom\u011B s teplovzdu\u0161n\u00FDm vyt\u00E1p\u011Bn\u00EDm."@cs . "SIMULATION OF THERMAL COMFORT IN A LOW-ENERGY FAMILY HOUSE WITH WARM-AIR HEATING"@en . . "thermal comfort, warm-air heating, draught risk"@en . "Simulace tepeln\u00E9 pohody v n\u00EDzkoenergetick\u00E9m rodinn\u00E9m dom\u011B s teplovzdu\u0161n\u00FDm vyt\u00E1p\u011Bn\u00EDm." . . "[5A5554778143]" . "Kos, Jan" . "2"^^ . . "\u010Cl\u00E1nek se zab\u00FDv\u00E1 simulac\u00ED tepeln\u00E9 pohody v hlavn\u00ED obytn\u00E9 m\u00EDstnosti n\u00EDzkoenergetick\u00E9ho rodinn\u00E9ho domu s teplovzdu\u0161n\u00FDm vyt\u00E1p\u011Bn\u00EDm, s n\u00EDm\u017E nejsou v na\u0161\u00ED zemi zat\u00EDm p\u0159\u00EDli\u0161 velk\u00E9 zku\u0161enosti. Vzhledem k mo\u017En\u00E9mu riziku pr\u016Fvanu jsou vyhodnoceny p\u0159edev\u0161\u00EDm rychlosti proud\u011Bn\u00ED vzduchu a jim odpov\u00EDdaj\u00EDc\u00ED stupe\u0148 obt\u011B\u017Eov\u00E1n\u00ED pr\u016Fvanem (DR) podle normy \u010CSN EN ISO 7730. Vypo\u010Dten\u00E9 rychlosti proud\u011Bn\u00ED vzduchu ve v\u00FD\u0161ce 10 cm nad podlahou se ve v\u011Bt\u0161in\u011B prostoru pohybuj\u00ED pod 0,2 m/s, \u010Demu\u017E odpov\u00EDdaj\u00ED hodnoty DR do 20 %. Jist\u00E9 riziko pocitu pr\u016Fvanu lze tedy o\u010Dek\u00E1vat. Ve v\u00FD\u0161ce 110 cm je situace p\u0159\u00EDzniv\u011Bj\u0161\u00ED - zde jsou hodnoty ukazatele DR vesm\u011Bs zanedbateln\u00E9." . . . "P(GA103/07/0907)" . "2"^^ . "Simulace tepeln\u00E9 pohody v n\u00EDzkoenergetick\u00E9m rodinn\u00E9m dom\u011B s teplovzdu\u0161n\u00FDm vyt\u00E1p\u011Bn\u00EDm." . "2008-11-06+01:00"^^ . . "RIV/00216305:26210/08:PU83474!RIV10-GA0-26210___" . . . "RIV/00216305:26210/08:PU83474" . "IBPSA-CZ" . "Kongresov\u00E9 centrum Hotel Continetal Kounicova 6" . "26210" . . "4"^^ . "\u010Cl\u00E1nek se zab\u00FDv\u00E1 simulac\u00ED tepeln\u00E9 pohody v hlavn\u00ED obytn\u00E9 m\u00EDstnosti n\u00EDzkoenergetick\u00E9ho rodinn\u00E9ho domu s teplovzdu\u0161n\u00FDm vyt\u00E1p\u011Bn\u00EDm, s n\u00EDm\u017E nejsou v na\u0161\u00ED zemi zat\u00EDm p\u0159\u00EDli\u0161 velk\u00E9 zku\u0161enosti. Vzhledem k mo\u017En\u00E9mu riziku pr\u016Fvanu jsou vyhodnoceny p\u0159edev\u0161\u00EDm rychlosti proud\u011Bn\u00ED vzduchu a jim odpov\u00EDdaj\u00EDc\u00ED stupe\u0148 obt\u011B\u017Eov\u00E1n\u00ED pr\u016Fvanem (DR) podle normy \u010CSN EN ISO 7730. Vypo\u010Dten\u00E9 rychlosti proud\u011Bn\u00ED vzduchu ve v\u00FD\u0161ce 10 cm nad podlahou se ve v\u011Bt\u0161in\u011B prostoru pohybuj\u00ED pod 0,2 m/s, \u010Demu\u017E odpov\u00EDdaj\u00ED hodnoty DR do 20 %. Jist\u00E9 riziko pocitu pr\u016Fvanu lze tedy o\u010Dek\u00E1vat. Ve v\u00FD\u0161ce 110 cm je situace p\u0159\u00EDzniv\u011Bj\u0161\u00ED - zde jsou hodnoty ukazatele DR vesm\u011Bs zanedbateln\u00E9."@cs . . "Praha" . "978-80-254-3373-7" . . "394809" .